Steam Boiler Low Water and High Water: Correct Handling Measures

2012/09/05

Latest company news about Steam Boiler Low Water and High Water: Correct Handling Measures

Correct Response Measures for Boiler Low Water Level (Water Level Below the Minimum Safe Water Level Line)

Indications:

  • The water level gauge reads below the minimum scale, and the low‑water alarm is triggered.
  • Steam temperature rises, and the steam flow rate exceeds the feedwater flow rate.
  • In severe cases, the waterwall tube wall temperature exceeds its limit, and abnormal sounds (such as those from overheating and deformation of tube walls) are heard in the furnace.

Measures:

  1. Immediately shut down the boiler; close the fuel valve and stop the forced‑draft fan, but keep the induced‑draft fan running (to expel residual heat from the furnace).
  2. Strictly prohibit adding water to the boiler (to prevent tube wall rupture due to uneven thermal expansion/contraction).
  3. Investigate the cause of low water level (e.g., feedwater valve blockage, feedwater pump failure, blowdown valve left open, etc.).
  4. After the boiler has cooled to ambient temperature, inspect the heating surfaces such as waterwall tubes for any damage.
  5. If no damage is found, correct the cause, then refill water, raise pressure, and resume operation per standard procedures. If damage is found, take the boiler out of service for repairs.

Correct Response Measures for Boiler High‑Water Level Accident (Water Level Above the Maximum Safe Water Level Line)

Indications:

  • The water level gauge reads above the maximum scale, and the high‑water alarm is triggered.
  • Steam temperature drops, and steam carryover occurs (with water‑hammer sounds in the steam piping).
  • Feedwater flow exceeds steam flow; in severe cases, steam quality deteriorates (e.g., increased salinity).

Measures:

  1. Immediately close the feedwater valve and stop the feedwater pump.
  2. Fully open the continuous blowdown valve and the intermittent (bottom) blowdown valve to rapidly reduce the water level.
  3. Open the steam line drain valves to remove accumulated condensate and prevent water hammer.
  4. Identify the cause of the high water level (e.g., feedwater valve sticking, faulty water level gauge, operator error).
  5. After the water level returns to normal, close the blowdown valves, restart the feedwater pump, and adjust the feedwater flow.
  6. If steam carryover is severe, reduce the boiler load until the steam quality meets the required standard.